D-AM 150 Display module

D-AM 150 Display module

D-AM 150 Display module.

Extension module for the D-GF 150 automatic firing device with functions ranging from first out annunciator to plain text display up to fieldbus communication.

Specifications

Ambient temperatures
-20 ... +60°C
Bus protocol
Modbus RTU
Protection class
IP20
Supply voltage
115/230V AC, 50/60 Hz
Dimensions (H x W x D)
130 x 170 x 114mm
Display
Alphanumeric LCD display
Weight
1.2 kg
Operational mode
Intermittent operation, continuous operation and 72-hour operation without permanent supervision
Electrical safety
Fail-safe

Downloads

The D-AM 150 display module upgrades the burner control D-GF 150 with:

  • A plain text display (LCD) for showing the current program cycle of the burner control as well as the remaining run-time
  • The supported user displays include: *Flame signal*, *Error message*, *Operational hours of the burner*, *Burner cycles*, *Date and time*
  • A first out annunciator for the continuous monitoring of all connected limiters and monitor chains. Should the system be shut down, the position in which chain the shutdown is performed is stored
  • A MODBUS interface for outputting status and process information for the burner and D-GF 150 burner control.

Features:

  • Plain text display for the burner control D-GF 150
  • Initial value indicator with 24 inputs in three groups
  • Fault memory
  • Text editor for plain text display
  • Output relay for control via Fieldbus
  • Operational hours counter
  • Cycle counter
  • Chip card for ease of programming
  • Fieldbus communication (MODBUS-RTU) for up to 32 devices
  • Can be combined with D-GF 150 as well as D-GF 150-MB

Applications:

  • Chemical industry
  • Refineries
  • Cement plants
  • Waste incinerators
  • Steam generators
  • Heating plants