D-GF 150 Burner control
D-GF 150 Burner control
D-GF 150 Self-monitoring and fail-safe burner control for the control of gas and oil burners as well as combined gas / oil burners of any capacity.
Generally used fuel types and burners require certain synchronised program cycles and safety times for burner start-up which are controlled and monitored electronically with the burner control.
The following program cycles may be selected on the D-GF 150 automatic firing device:
- Gas fuel with boiler pre-purge
- Gas fuel without boiler pre-purge
- Oil fuel with boiler pre-purge
- Oil fuel without boiler pre-purge
Specifications
Ambient temperatures
-20 ... +60°C
Bus protocol
Modbus
Protection class
IP20
Supply voltage
115/230V AC, 50/60 Hz
Analogue outputs
0/4 ... 20mA
Dimensions (H x W x D)
130 x 170 x 114mm
Display
LED
Weight
1.5 kg
Operational mode
Intermittent operation, continuous operation and 72-hour operation without permanent supervision
Electrical safety
Self-monitoring and fail-safe
Downloads
Brochures
Certificates
Features:
- Controlling and monitoring of gas and oil burners of any capacity
- Suitable for intermittent operation as well as continuous operation
- Integrated gas valve monitoring system
- Separate outputs for control of gas and oil fuel valves
- Quick fuel change “on the fly” without burner shut down
- Adjustable pre-purge timer
- Integrated flame monitor
- Input for external flame monitor
- Data interfaces
- Status displays (LED or text)
Applications:
- Chemical industry
- Refineries
- Cement plants
- Waste incinerators
- Steam generators
- Heating plants