D-LE 603 Flame sensor

D-LE 603 Flame sensor

D-LE 603 Flame sensor (flame scanner) for monitoring gas, oil and coal flames, primarily in multi-burner view applications.

The photo element in the flame sensor generates a signal which is proportional to the flame radiation intensity. The output signal of the flame sensor is used as an input signal to a control unit or a burner control. The D-LE 603 flame sensor is available with different photo elements for maximum selectivity when using various fuels.


Features:

  • Self-monitoring and fail-safe in conjunction with a control unit / burner control
  • Flame sensors for every spectral range from UV to IR
  • Connection to the D-UG 120 control unit, D-UG 660 control unit as well as to the D-GF 150 (-MB) burner control
  • Uniform output signal thus mutually interchangeable
  • Adjustable to different combustion technologies such as exhaust gas recirculation
  • Compliance to general safety regulations
  • ATEX approved (D-LE 603 …/94 Ex for zone 1 and D-LE 603 …/97Ex for zone 2)

Applications:

  • Power stations
  • Chemical industry
  • Refineries
  • Cement plants
  • Waste incinerators
  • Steam generators
  • Heating plants

Specifications

Ambient temperatures
-20 ... +60°C
Protection class
IP65
EX approval
Optional: II 2G EEx de IIC T5/T6 / II 3G EEx nC T5/T6
Supply voltage
24V DC
Dimensions (H x W x D)
90 x 92 x 350mm
Viewing angle

Purge air connection
G ½“
Weight
1.8 kg
Operational mode
Intermittent operation, continuous operation and 72-hour operation without permanent supervision
Electrical safety
Self-monitoring and fail-safe in conjunction with a control unit/burner control